Digital I/O-Module for KAM-PRO with 8-In-/Outputs

Price after login/registration

Available, delivery time 2-5 Tage

Request an offer
Product number: KIO7052
GTIN/EAN: 4260300580343
Weight: 0.3 kg
The I/O expansion module connects to an AlarmManager-PRO and is used to connect external alarm messages. The communication takes place via Ethernet. Thus, the module can be mounted at any location. The configuration is done in the web interface of the AlarmManager-PRO.

8 digital in- and outputs (e.g. air conditioning, UPS system, external sensors, etc.)

Up to 32 modules (max. 500 alarm inputs) can be operated on one AlarmManager-PRO.
Connectivity: Ethernet 10/100Mbit and PoE
Variant: Extension
de

current93612d0c-59d6-4e5f-bfe9-da1b4674ca92PDF-ExportScroll PDF Exporter

SINK
Readback as 1
+10 ~ +50VDC


SOURCE
Readback as 1
+10 ~ +50 VDC

DIGITAL OUTPUT
ON State
Readback as 1

SINK
Readback as 0
OPEN or <4 VDC

SOURCE
Readback as 0
OPEN or <4 VDC


DIGITAL OUTPUT
OFF State
Readback as 0


Funktionsbeschreibung

Erweiterungsmodul zum Anschluss an den AlarmManager-PRO. Das Modul erweitert die externen Ein-Ausgänge des AlarmManagers auf zusätzlich 8 digitale Eingänge und 8 digitale Ausgänge. Die Kommunikation erfolgt über Ethernet, somit kann das Modul an beliebiger Stelle montiert werden. Die Konfiguration erfolgt in der Softwareoberfläche des AlarmManager-PRO. Das Modul bietet über den integrierten Web-Server eine einfache IP Konfiguration und den Test der Ein-Ausgänge ohne zusätzliche Software.

Anschlussmöglichkeit

Externe Alarme von bestehenden Systemkomponenten (Klimageräte, USV-Systeme, Generatoren, Alarmsysteme)

AlarmManager

Anschluss an Kentix AlarmManager-PRO

Konfiguration

Integr. Web-Server (HTTP), Default IP: 192.168.255.1 (Admin/Admin)

Protokolle

KAM-IO Kommunikation über IP-Port: 502 (Default)

Sicherheit

ID, Passwort und IP-Filter

Anschlussklemmen

Steckbare Schraubklemmen für Kabel bis 1mm²

Eingänge

Digitale Eingänge für Spannungsbeschaltung

ON: +10-50VDC, OFF: +4DC

Eingangsimpedanz: 10kOHM, Überspannungsschutz 70VDC

Ausgänge

Open-Collector Ausgänge 10-40VDC

Belastbarkeit 650mA (bis 1.1A Überstromschutz)

Überspannungsschutz 47VDC

Belegung Alarmausgänge

DO1-DO8: Zuordnung über AlarmManager-Konfiguration

Isolierung

Ethernet 1,5kVDC, I/O 3,7kVrms

Umgebung

Betriebstemperatur 0°C bis +45°C, Rel. Luftfeuchtigkeit 10-90%

Netzwerk

LAN 10/100 Base-TX

Spannungsversorgung

Externes Netzteil 12-30VDC, 4.3Watt

Gehäuse

72 x 123 x 35 mm (DIN-Schienen Montage)

Lieferumfang

KIO7052, 3m Patchkabel, Power-Anschlusskabel, Anleitung

Zulassung

CE














en

current93612d0c-59d6-4e5f-bfe9-da1b4674ca92PDF-ExportScroll PDF Exporter


SINK
Readback as 1
+10 ~ + 50VDC

SOURCE
Readback as 1
+10 ~ + 50VDC

DIGITAL OUTPUT
ON State
Readback as 1

SINK
Readback as 0
OPEN or <4 VDC

SOURCE
Readback as 0
OPEN or <4 VDC

DIGITAL OUTPUT
OFF State
Readback as 0


Description

Expansion module for connection to the AlarmManager-PRO. This module extends the external inputs and outputs on the AlarmManager by additional 8 digital inputs and 8 digital outputs. Communication is done by Ethernet, so the module can be mounted anywhere. The configuration is done in the software interface of the AlarmManager-PRO. The module provides a built-in web server for simple IP configuration and testing of the inputs and outputs without any additional software.

Connectivity

External alarms from existing system components (air conditioners, UPS systems, generators, alarm systems)

AlarmManagerConnection to Kentix AlarmManager-PRO

Configuration

Built-in web server (HTTP), Default IP: 192.168.255.1 (Admin/Admin)

Protocols

KAM-IO communication through IP port: 502 (Default)

Security

ID, password and IP filter

Terminals

Pluggable screw-terminal for cables up to 1mm²

Inputs

Digital Inputs for voltage circuitry

ON: +10-50VDC, OFF: +4DC

Input impedance: 10kOHM, over voltage protection: 70VDC

Outputs

Open collector outputs 10-40VDC

Current load capacity 650mA (up to 1.1A overcurrent protection)

Overvoltage protection: 47VDC

Alarm output assignment

DO1-DO8: assignment via AlarmManager configuration

Isolation

Ethernet 1,5kVDC, I/O 3,7kVrms

Environment

Operation temperature 0°C to +45°C, rel. humidity 10-90%

Network

LAN 10/100 Base-TX

Power supply

External power supply 12-30VDC, 4.3W

Chassis

72 x 123 x 35 mm (DIN-rail mounting)

Content of delivery

KIO7052, 3m patch-cable, power-cable, manual

Approvals

CE


  • 1 IO module
  • 1 DIN rail adapter
  • 1 SlimLine cable 3m

Accessories


Accessories

LAN
RADIO
4G
AlarmManager-PRO (Black)
  • Up to 500 MultiSensors
  • Monitored hazards: up to 19
  • Web server - App - Kentix360
  • SMS - Email - SNMP
  • Integrated LTE Modem
  • Integrated UPS

Price after login/registration

Log in or register now
LAN (PoE)
RADIO
4G
API
VDS2465
StarterSet-PRO SmartMonitoring (Black)
  • Up to 500 MultiSensors
  • Monitored hazards: up to 37
  • Web server - App - Kentix360
  • SMS - Email - SNMP
  • Up to 1.000 alarm receivers
  • Room monitoring up to 10.000m²

Price after login/registration

Log in or register now
SYS
Magnet Door-Contact, white, 2m cable with RJ45 for Kentix-Systemport
  • Opening detector
  • Connection to system socket
  • Cable length 2m

Price after login/registration

Log in or register now

Related Products


Related Products

LAN
PoE
Digital I/O-Module for KAM-PRO with 16-Inputs
  • 16 digital inputs
  • connection of external alarm messages
  • Integrated web server
  • Power over Ethernet

Price after login/registration

Log in or register now
LAN
PoE
Analog-Module for KAM-PRO with 8-Inputs and 4 digital-outputs
  • 8 analog in- and 4 outputs
  • connection of external alarm messages
  • Integrated web server
  • Power over Ethernet

Price after login/registration

Log in or register now
SYS
I/O relais adapter for Kentix sytem port
  • I/O adapter
  • 2 digital inputs
  • 2 relay outputs

Price after login/registration

Log in or register now